Electrical requirements for R22 8/6 Series models

FDT 8 Series ceiling cassette
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
2088
8.1
44
1ph 20A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
2588
9.4
51
1ph 30A
3088
14.4
95
1ph 30A
3088
5.5
45
3ph 15A/ph
4088
8.1
53
3ph 15A/ph
5088
10.3
74
3ph 20A/ph

Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
2086
9.8
47
1ph 20A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
2586
13.2
64
1ph 30A
3086
16.3
89
1ph 30A
3086
6
43
3ph 15A/ph
4086
8.8
45
3ph 15A/ph
5086
11
68
3ph 20A/ph

FDKN 8 Series wall mounted
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
2088
8
44
1ph 20A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
2588
9.3
51
1ph 30A
3088
14.4
95
1ph 30A
3088
3ph 15A/ph

3086
16.2
89
1ph 30A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
3086
5.9
43
3ph 15A /ph

FDEN 8 Series ceiling suspended
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
2088
8
44
1ph 20A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
2588
9.4
51
1ph 30A
3088
14.4
95
1ph 30A
3088
5.5
45
3ph 15A/ph
4088
7.9
53
3ph 15A/ph
5088
10.1
74
3ph 20A/ph

3086
16.3
89
1ph 30A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
3086
6.1
43
3ph 15A /ph
4086
8.6
45
3ph 15A/ph
5086
10.8
68
3ph 20A/ph

FDR 8 Series ducted cassette
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
2088
8.1
44
1ph 20A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
2588
9.4
51
1ph 30A
3088
14.5
95
1ph 30A
3088
5.6
45
3ph 15A/ph
4088
7.9
53
3ph 15A/ph
5088
10.2
74
3ph 20A/ph

3086
16.4
89
1ph 30A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
3086
5.4
43
3ph 15A /ph
4086
7.3
45
3ph 15A/ph
5086
9.9
68
3ph 20A/ph

FDU 8 Series ducted (horizontal)
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
3088
15.4
95
1ph 30A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
3088
6.2
45
3ph 15A/ph
4088
8.4
53
3ph 15A/ph
5088
10.6
74
3ph 20A/ph
808
15.5
99
3ph 32A/ph
1008
21.8
154
3ph 32A/ph

3086
17.3
89
1ph 30A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
3086
7.1
43
3ph 15A /ph
4086
9.4
45
3ph 15A/ph
5086
11.5
68
3ph 20A/ph

SRK Wall mounted - heat pump
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
208
3.6
18.9
1ph 15A
Indoor Unit
4 wires + Earth for Heat Pump
(all mains voltage)
258
3.4
18.9
1ph 15A
288
4.6
19.6
1ph 15A
328
6.9
36.6
1ph 15A
408
6.4
36.6
1ph 15A
508
8.2
52.4
1ph 20A
568
9.53
48.2
1ph 20A
501
8.2
42
1ph 20A
561
9.53
48
1ph 20A

SRK Wall mounted - cooling only
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
208
2.6
12.8
1ph 15A
Indoor Unit
2 wires + Earth for Cooling Only
(all mains voltage)
258
3.4
18.9
1ph 15A
288
4.2
19.6
1ph 15A
328
4.4
19.6
1ph 15A
408
6.4
36.6
1ph 15A
508
8.2
52.4
1ph 20A
568
9.53
48.2
1ph 20A
501
8.2
42
1ph 20A
561
9.53
48
1ph 20A

Electrical requirements for R407C 8 Series models

FDT 8 Series ceiling cassette
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
2088
9.7
55
1ph 20A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
2588
12.6
63
1ph 30A
3088
15.3
95
1ph 30A
3088
5.8
45
3ph 15A/ph
4088
8.4
53
3ph 15A/ph
5088
10
74
3ph 20A/ph

FDKN 8 Series wall mounted
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
2088
9.5
55
1ph 20A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
2588
12.3
63
1ph 30A
3088
15.2
95
1ph 30A
3088
5.7
43
3ph 15A/ph

FDEN 8 Series ceiling suspended
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
2088
9.6
55
1ph 20A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
2588
12.6
63
1ph 30A
3088
15.3
95
1ph 30A
3088
5.8
45
3ph 15A/ph
4088
8.2
53
3ph 15A/ph
5088
9.8
74
3ph 20A/ph

FDR 8 Series ducted cassette
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
2088
9.7
55
1ph 20A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
2588
12.6
63
1ph 30A
3088
15.3
95
1ph 30A
3088
5.8
45
3ph 15A/ph
4088
8.4
53
3ph 15A/ph
5088
10
74
3ph 20A/ph

FDU 8 Series ducted (horizontal)
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
2088
15.4
95
1ph 30A
Outdoor Unit
3 wires + Earth for Cooling Only
5 wires + Earth for Heat Pump (all mains voltage)
0.75mm2 to 1.5mm2
3088
6.2
45
3ph 15A/ph
4088
8.4
53
3ph 15A/ph
5088
10.6
74
3ph 20A/ph

Electrical requirements for R407C SRK Series models

SRK Wall mounted - heat pump
Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
288
4.6
19.6
1ph 15A
Indoor Unit
4 wires + Earth for Heat Pump (all mains voltage)
408
6.4
36.6
1ph 15A

SRK Wall mounted - cooling only

Model No.
Run Current (A)
Start Current (A)
Power Supply
Mains Supply to
Interconnecting Wiring
258
3.4
18.9
1ph 15A
Indoor Unit
2 wires + Earth for Cooling Only (all mains voltage)
288
4.3
19.6
1ph 15A
408
6.4
36.6
1ph 15A

KX2 & KXR Electrical Data - mains power supplies

Outdoor units 3 phase - power supply details
Model Ref
System Type
Power Supply
Max. Inrush Current
Max. Run Current
MCB Rating (Motor 'D' Rated)
FDC1251HKXES
2-pipe
3 ph + N
5 A/ph
12.9 A/ph
16 A/ph
FDC2001HKXES
2-pipe
3 ph + N
5 A/ph
15.8 A/ph
32 A/ph
FDC2501HKXES
2-pipe
3 ph + N
5 A/ph
21.0 A/ph
32 A/ph

FDCJ140 KX2
2-pipe
3 ph + N
5 A/ph
10.2 A/ph
16 A/ph
FDCJ224 KX2
2-pipe
3 ph + N
48 A/ph
14.6 A/ph
32 A/ph
FDCJ280 KX2
2-pipe
3 ph + N
70 A/ph
19.0 A/ph
32 A/ph

FDC2001HKXR
3-pipe
3 ph + N
5 A/ph
15.8 A/ph
32 A/ph*
FDC2501HKXR
3-pipe
3 ph + N
5 A/ph
21.0 A/ph
32 A/ph*
*please note: A supplementary transformer is fitted to the incoming power wiring on KXR units, which may result in a current surge on initial connection. In most circumstances the 32A/ph MCB rating is sufficient to handle the normal starting current of the outdoor unit. Once the transformer is powered, the start current is 5 A/ph. This does not apply to KX2 outdoor units.
Indoor units single phase - running current (at 240V)
Model Ref
KX2 model Ref
Model No.
201
251
321
401
501
631
801
1001
1251
22
28
36
45
56
71
90
112
140
Run Current (A)
FDT Cassette 4-way
-
-
0.44
0.44
0.49
0.49
0.50
0.55
0.81
1.02
FDTS Cassette 1-way
-
-
0.36
0.36
0.46
-
0.63
-
-
-
FDTW Cassette 2-way
-
-
0.42
-
0.42
0.42
0.44
0.65
0.98
1.13

FDR Ducted Cassette
-
0.46
0.56
-
0.67
0.67
0.71
0.79
1.17
1.32
FDUM Horizontal Ducted
-
-
-
0.67
0.67
0.67
0.71
0.79
1.17
1.32
FDE Ceiling Suspended
-
-
-
0.46
0.46
0.46
0.63
-
0.98
1.20

FDKY Wall Mounted
-
-
0.28
0.28
0.33
0.39
0.48
-
-
-
FDFL Floor Mounted
-
-
0.42
-
0.42
-
0.48
-
-
-

Power supply to indoor units - recommended 5A fused supply. Groups of units, say up to 8 or 10 units, can be wired to a ring main (MCB 16A), but must have individual isolators and fuse/MCB.
For CONTROL WIRING please refer to KX2/KXR Engineering Data manual or system schematics.